| no | item | operational standards and limitation | |||
|---|---|---|---|---|---|
| refrigerant | R22 (normal) | R407C | R410A | R22 (tropical) | |
| 1 | Condensing temp (pressure)[°C] [kg/cm².G] |
28~65 | 28~75 | ||
| 10.5~26.5 | 10.1~27.5 | 17.2~42.3 | 10.5~32.0 | ||
| 2 | Evaporating temp (pressure)[°C] [kg/cm².G] |
-25.0~12.7 | |||
| 1.02~6.5 | 0.71~6.0 | 2.33~10.9 | 1.02~6.5 | ||
| 3 | Compression ratio | 2~8 | |||
| 4 | Suction gas superheat | Sufficient superheat is proffered for preventing liquid flood back | |||
| 5 | Liquid subcool | Sufficient liquid subcool is proffered | |||
| 6 | Discharge gas temp | Max. 115°C | |||
| 7 | Motor winding temp. | Max. 130°C | |||
| 8 | Bottom shell temperature | Min. 5 °C higher than condensing temp | |||
| 9 | Abnormal pressure rise | Max. 48.0kg/cm²·G | |||
| 10 | On-Off cycle | On/Off= Min. 3 Minutes / Min. 3 Minutes → Total 200,000 cycles | |||
| 11 | Oil level | Steady-state : higher than 5mm based bottom plane of cylinder Transient-state : higher than bottom plane of bottom flange | |||
| 12 | Vibration of tubing | Steady-state : higher than 5mm based bottom plane of cylinder Transient-state : higher than bottom plane of bottom flange | |||
| 13 | Tube stress | Starting & stop : less than 3.5 kg/mm² Normal operating : less than 1.25 kg/mm² |
|||
| 14 | Spacing of tubing | Between tube and moving parts : Min. 13.0 mm Between tube and non-moving parts : Min. 10.0 mm |
|||
| 15 | Length of tubing | Max. 15m between indoor and outdoor sections (Need to the special discussion in case of excess) |
|||
| 16 | Height difference of tubing | Max. 7m between indoor and outdoor sections (Need to the special discussion in case of excess) |
|||
| 17 | Tilt of operation | The allowable tilt of compressor under operation should be 5째 or less | |||
| 18 | Storage | Do not open compressor rubber plugs more than 10 minutes before use Max. storage time : 1 year from manufacturing | |||
| 19 | External shock | External shock should be less than 60 G | |||
| 20 | Prohibition of air or | Do not operate the compressor in air or vacuum | |||
| 21 | Vacuum operating | Less than ( Oil Volume * Oil density ) / ( 0.35 ~ 0.4 ) | |||