AM120FXWANR/EU

DVM S, Water cooled, 33.6kW Condenser

Water Cooling Dual Inverter Compressor Flexible Installation

Samsung DVM S Water

Water Cooling

The DVM S WATER is a cooling & heating system for buildings that uses water as its heat source, with connections to cooling towers and boilers, or alternatively to geothermal source. Samsung water cooled VRF provides stable and reliable performance with minimal effect from ambient conditions. It offers versatility with the ability to connect multiple indoor units and a wide variety of indoor types to choose from. Samsung DVM S Water source VRF units area a great option for retro-fit or new constructions.

Samsung DVM S Water

High efficiency

Dual Inverter Compressors

The DVM S WATER air conditioning system provides efficient and powerful performance. Its innovative Dual Inverter Compressor, with a high efficiency Vapor Injection System, ensures powerful, rapid cooling and heating.

*Tested on AM300KXWANR*** compared with Samsung conventional model AM300KXVAGH***
*Tested on AM300KXWANR*** compared with Samsung conventional model AM300KXVAGH***

Flexible installation almost anywhere

Flexible Installation

The DVM S WATER can be install with great flexibility; It has an allowable piping length of up to 170 meters between the outdoor and indoor units, and a height of separation of up to 50 meters.

*Max height and length may vary by combination of IDU and ODU

Flexible installation almost anywhere

*Max height and length may vary by combination of IDU and ODU

Precise Control

Independently Cool & Heat

Heat Recovery systems add the capability to heat and cool separate zones simultaneously, making DVM S WATER an excellent choice.

Independently cool and heat

Optimum water flow controller

Built-in Water Flow logic

The DVM S WATER’s built-in Water Flow Controller helps to control the amount of water required to cool and heat the outdoor unit, it determines the water flow required based on the internal temperature of the spaces, hence assisting with water pump power efficiency.

Quiet comfort

Minimal noise level

The DVM S WATER outdoor unit has a low operating noise level, as it uses a water-cooled Plate Heat Exchanger for system heat rejection, there is no outdoor fan, reducing the sound impact on your building’s working environment.

* Tested on AM200FXWANR*** compared with Samsung conventional model AM200KXVAGH**** Sound Pressure level is a relative value, depending on the distance and acoustic environment.* Sound Power Level Measured according to ISO 3741.

Minimal noise for maximum comfort

* Tested on AM200FXWANR*** compared with Samsung conventional model AM200KXVAGH**** Sound Pressure level is a relative value, depending on the distance and acoustic environment.* Sound Power Level Measured according to ISO 3741.

reasons to partner with Samsung

reasons to partner with Samsung
Specification
  • Technical Information
    • Type DVM S Water&GEO(NEW)
  • Model Name
    • Outdoor Unit AM120FXWANR/EU
  • Power Supply (Outdoor Unit) [Φ, #, V, Hz]
    • 3,4,380-415,50/60
  • Airflow
    • Mode HEAT RECOVERY
  • Performance (nominal)
    • 12.00 HP
  • Capacity
    • Cooling (Min / Std / Max) 33.60 kW
    • Cooling [Btu/h] 114,600 Btu/h
    • Heating (Min / Std / Max) 37.80 kW
    • Heating [Btu/h] 129,000 Btu/h
  • Power Input (Nominal)
    • Cooling 1) [W] 6.46 W
    • Heating 2) [W] 6.51 W
  • Current Input (Nominal)
    • Cooling 1) 10.30 A
    • Heating 2) 10.40 A
  • Circuit Amps
    • MCA 25.00 (MCA)
    • MFA [A] 30.00 A
  • Energy Efficiency
    • EER (Std, Cooling) 5.20
    • COP (Std, Heating) 5.81
  • Compressor
    • Type SSC Scroll x 1
    • Output(kW) (6.39)
    • Model DS-GB066FAVB x 1
    • Oil (Type) PVE
    • Oil (Initial Charge) [cc] 1100 cc
  • Condenser
    • Type PHE(Stainless Steel Plate)
    • Pipe Size (Φ, inch) 32.0"
    • Lost Head (kPa) 43.0
    • Water Flow Rate (LPM) 114.0 LPM
    • Max. Pressure (Mpa) 1.96
  • Piping
    • Liquid Pipe (Φ, mm) 12.70 mm
    • Liquid Pipe (Φ, inch) 1/2"
    • Gas Pipe (Φ, mm) 28.58 mm
    • Gas Pipe (Φ, inch) 1 1/8"
    • Discharge Gas Pipe (Φ, mm) 19.05 mm
    • Discharge Gas Pipe (Φ, inch) 3/4"
    • Oil Equalizing Pipe (Φ, mm) -
    • Oil Equalizing Pipe (Φ, inch) -
    • Installation Max. Length [m] 170 m
    • Installation Max. Height [m] 50.0 m
  • Power Supply
    • Indoor (V) 4
    • Outdoor (V) 0.75 ~ 1.25
  • Refrigerant
    • Type R410A(Fluorinated greenhouse gas, GWP=2,088) 12.53tCO2e
    • Factory Charging (kg) 6.00 kg
  • Noise Level (Outdoor)
    • Sound Pressure 50.0 dBA
    • Sound Power 70.0 dBA
  • External Dimension (Outdoor Unit)
    • Net Weight (Indoor) 160.0 kg
    • Net Weight (Outdoor) 167.0 kg
    • Unit Dimension (Indoor, WxHxD) 770 x 1,000 x 545 mm
    • Unit Dimension (Outdoor, WxHxD) 840 x 1,200 x 620 mm
  • Operating Temp. Range
    • Cooling (℃) 10.0 ~ 45.0 ℃
    • Heating (℃) 10.0 ~ 45.0 ℃
Manual Download

DVM S, Water cooled, 33.6kW Condenser (AM120FXWANR/EU)

Manuals

2019.01.15

Installation Guide ver 1.0

(ENGLISH)