AM100FNKDEH/EU

DVM, ERV Plus, Heat Pump

Get Fresh Air without Temperature Loss Maintatin the Best Indoor Humidity Level Smart CO2 Sensor and Humidity Stat
Capacity 11.5kW, 1000m3/hr

ERV Plus System Structure

Supply / Exhaust Fan: Takes in air from outdoors or exhausts stale air from indoors.
Temperature Sensor: Automatic detection of indoor and outdoor temperature, enabling a switch to auto mode or executing the cold climate control function.
Dust Filter: Prevents dust from accumulating and blocking or contaminating the heat exchanger element.
Heat Exchanger Element: Transfers heat from exhaust air to fresh air for maximum efficiency.
Control Box: Contains electrical parts for product control.
Humidifier Element (Optional): A natural evaporating-type humidifier produces more refreshing indoor air.
Direct Expansion (DX) Coil: The new DX Coil heats and cools, enabling mode selection when ventilation is on.
Damper: Users can select between heat recovery and normal ventilation.

ERV Plus System Structure

*Availability of these features varies according to the type of model.

Energy Saving Operation

The ERV system changes the operation mode automatically depending on the outdoor and indoor temperature. This feature enables businesses to benefit from considerable energy savings, no matter what the conditions. In extreme climates with larger discrepancies, the unit operates as an ERV. When the differences between inside and outside are minor, it functions as a conventional ventilation fan, saving money. This product, combined with air conditioners, delivers world-class energy-saving solutions to intelligently reduce the cooling and heating load while maintaining optimised performance.

Energy Saving Operation

New Diamond Type Heat Exchanger

Compact and extremely efficient, the new diamond-type heat exchanger is designed to optimise airflow. Compared to conventional rectangular and hexagonal models, it delivers fresh air and maintains a comfortable, stable and eco-friendly performance. Businesses will benefit from reduced costs and a comfortable environment.

New Diamond Type Heat Exchanger
Specification
  • Features
    • Type ERV PLUS
  • Model Name
    • Indoor Unit AM100FNKDEH/EU
  • Power Supply (Indoor Unit) [Φ, #, V, Hz]
    • 1, 2, 220 - 240, 50
  • System
    • Mode HP / HR
  • Capacity
    • Cooling [kW] 7.10 kW
    • Cooling [Btu/h] 24200 Btu/h
    • Heating [kW] 8.00 kW
    • Heating [Btu/h] 27300 Btu/h
  • Power Input (Nominal)
    • Cooling 1) [W] 510.00 W
    • Heating 2) [W] 510.00 W
  • Current Input (Nominal)
    • Cooling 1) 3.70 A
    • Heating 2) 3.70 A
  • Fan
    • Type Sirroco Fan / BLDC
    • Motor (Output) [W] 70 x 2 W
    • Air Flow Rate (High / Mid / Low) [CMM] 16.67 / 16.67 / 11.50 CMM
    • Air Flow Rate(High/Mid/Low)[L/S] 277.83 / 277.83 / 191.67
    • External Static Pressure (Min / Std / Max) [mmAq] 7.60 / 9.20 / 15.30 mmAq
    • External Static Pressure (Min / Std / Max) [Pa] 74.53 / 90.22 / 150.04 Pa
  • Piping Connections
    • Liquid Pipe (Φ, mm) 6.35 mm
    • Liquid Pipe (Φ, inch) 1/4"
    • Gas Pipe (Φ, mm) 12.70 mm
    • Gas Pipe (Φ, inch) 1/2"
    • Drain Pipe (Φ,mm) VP25 (OD 32,ID 25) mm
  • Field Wiring
    • Power Source Wire 1.5 ~ 2.5
    • Transmission Cable 0.75 ~ 1.50
  • Refrigerant
    • Type R410A
    • Control Method EEV INCLUDED
  • Sound
    • Sound Pressure (High / Mid / Low) [dB(A)] 36.0 / 34.0 / 31.0 dBA
    • Sound Power 67.0 dBA
  • External Dimension (Indoor Unit)
    • Net Weight(kg) 90.00 kg
    • Shipping Weight (kg) 107.50 kg
    • Net Dimensions (WxHxD) (mm) 1763 x 340 x 1135 mm
    • Shipping Dimensions (WxHxD) (mm) 2027 x 428 x 1424 mm
Manual Download

DVM, ERV Plus, Heat Pump (AM100FNKDEH/EU)

Manuals

1 Aug, 2017

User Manual ver 1.0

(ENGLISH)