AM120JXVHGR/ET

AM120JXVHGR/ET

Compact size High energy efficiency

Advanced performance & energy efficiency

Its advanced technology radically improves performance and reduces wasted energy. It includes a highly efficient Inverter Scroll Compressor, an innovative Hybrid heat exchanger and a large capacity diffuser.

Advanced performance & energy efficiency

Improved reliability in cold conditions

An advanced refrigerant control system ensures the compressor continues working reliably – even if everything is frozen. Its flash injection technology provides a great improvement in heating performance at -25°C.

Improved reliability in cold conditions

Instant shut off and gas leak protection

There’s no need to worry about gas leaks or the accidental loss of refrigerant. A Gas Leak Operation System quickly detects leaks and automatically takes the pump down a step and cuts off the refrigerant supply.

* Complies with the safety requirements of the BS-EN 378 standard.

Instant shut off and gas leak protection

* Complies with the safety requirements of the BS-EN 378 standard.

Flexibly install it almost anywhere

Provides the flexibility to be installed almost anywhere, regardless of its location or distance from the building. It has a piping length of up to 220m (721.79ft) and can reach up to a height of 110m (360.9ft).

Flexibly install it almost anywhere

Control your cooling anywhere

An optional Wi-Fi Kit lets you remotely control up to 16 indoor units using an App*. Anytime and anywhere you can turn them on and off, select the operating mode and temperature, and utilize their other functions.

* Available on iPhones and Android devices. A Wi-Fi connection is required.

Control your cooling anywhere

* Available on iPhones and Android devices. A Wi-Fi connection is required.

Specification
  • Features
    • Type DVM S (HR)
  • Model Name
    • Outdoor Unit AM120JXVHGR/ET
  • Power Supply (Outdoor Unit) [Φ, #, V, Hz]
    • 3,4,380-415,50
  • System
    • Mode HEAT RECOVERY
  • Performance (nominal)
    • 12 HP
  • Capacity
    • Cooling [kW] 33.6 kW
    • Heating [kW] 33.6 kW
  • Power Input (Nominal)
    • Cooling 1) 7.57 kW
    • Heating 2) 6.72 kW
  • Current Input (Nominal)
    • Cooling 1) 12.10 A
    • Heating 2) 10.80 A
  • Power
    • MCA [A] 25.0 A
    • MFA [A] 32 A
  • Energy Efficiency
    • EER (Nominal Cooling) 4.44
    • COP (Nominal Heating) 5.00
  • Compressor
    • Type 자작 Scroll Inverter
    • Output(kW) 6.39 x 1 kW
    • Model 66cc x 1
    • Oil (Type) PVE
    • Oil (Initial Charge) [cc] 1,100 x 1 cc
  • Fan
    • Type Propeller
    • Motor (Output) [W] 830 x 1 W
    • Air Flow Rate (High / Mid / Low) [CMM] 170 CMM
    • External Static Pressure (Min / Std / Max) [mmAq] 8.0 mmAq
  • Piping Connections
    • Liquid Pipe (Φ, mm) 12.7 mm
    • Liquid Pipe (Φ, inch) 1/2"
    • Gas Pipe (Φ, mm) 28.58 mm
    • Gas Pipe (Φ, inch) 1+1/8"
    • Installation Max. Length [m] 200(220)
    • Installation Max. Height [m] 50(110)/40(110)
  • Refrigerant
    • Type R410A(Contains fluorinated greenhouse gas, GWP=2,088)
    • Factory Charging (kg) 6.50 kg
    • Factory Charging (tCO2e) 13.57 tCO2e
  • Sound
    • Sound Pressure 62 dBA
    • Sound Power 83/85 dBA
  • External Dimension (Outdoor Unit)
    • Net Weight(kg) 201.0 kg
    • Shipping Weight (kg) 217.0 kg
    • Net Dimensions (WxHxD) (mm) 880 x 1,695 x 765 mm
    • Shipping Dimensions (WxHxD) (mm) 948 x 1,887 x 832 mm
  • Operating Temp. Range
    • Cooling (℃) -5 ~ 48 ℃
    • Heating (℃) -25 ~ 24 ℃