AM056FNCDEH/EU

DVM, Ceiling, Heat Pump R410a, Indoor Unit

Small package, big performance Choice of installation options
Capacity 5.6 kW
Two-Way Installation

Two-Way Installation

Two-Way Installation

The two-way installation option enables users to choose the best solution for their specific requirements. This flexible unit can be deployed under the ceiling or as a free-standing floor unit. If space is limited and airflow needs to come from above, the ceiling setting is ideal, while the floor-standing option is perfect when room is abundant. This two-way design is efficient, cost-effective and elegant.

Compact but Powerful

Compact but Powerful

Compact but Powerful

The Samsung Ceiling Type air conditioning unit is slim and compact, offering a wider choice of installation locations. At just half the size of competitor units, this air conditioning system's cooling power is comparable to larger products. Its smaller size and lighter weight mean your business benefits from reduced set-up costs.

Anti-Virus Filter

Anti-Virus Filter

Anti-Virus Filter

The anti-virus filter lets businesses and their users benefit from cleaner air in their premises. This feature is specifically designed to keep local air free from dust particles and to minimise the spread of mould spores and harmful bacteria. This generates a more comfortable and safe environment for business users.

Specification
  • Features
    • Type CEILING
  • Model Name
    • Indoor Unit AM056FNCDEH/EU
  • Power Supply (Indoor Unit) [Φ, #, V, Hz]
    • 1, 2, 220 - 240, 50
  • System
    • Mode HP / HR
  • Capacity
    • Cooling [kW] 5.6 
    • Cooling [Btu/h] 19,100 
    • Heating [kW] 6.3 
    • Heating [Btu/h] 21,500 
  • Power Input (Nominal)
    • Cooling 1) [W] 72 
    • Heating 2) [W] 72 
  • Current Input (Nominal)
    • Cooling 1) 0.33 A
    • Heating 2) 0.28 A
  • Fan
    • Type Sirocco Fan
    • Motor (Output) [W] 60 x 1 
    • Air Flow Rate (High / Mid / Low) [CMM] 14 / 13 / 12 
    • Air Flow Rate(High/Mid/Low)[L/S] 233.33 / 216.67 / 200
  • Piping Connections
    • Liquid Pipe (Φ, mm) 6.35 
    • Liquid Pipe (Φ, inch) 1/4"
    • Gas Pipe (Φ, mm) 12.7 
    • Gas Pipe (Φ, inch) 1/2"
    • Drain Pipe (Φ,mm) ID 18 HOSE
  • Field Wiring
    • Power Source Wire 1.5 ~ 2.5
    • Transmission Cable 0.75 ~ 1.5
  • Refrigerant
    • Type R410A (Fluorinated greenhouse gas)
    • Control Method EEV NOT INCLUDED
  • Sound
    • Sound Pressure (High / Mid / Low) [dB(A)] 40 / 37 / 34 
    • Sound Power 60 dBA
  • External Dimension (Indoor Unit)
    • Net Weight(kg) 21 
    • Shipping Weight (kg) 25.5 
    • Net Dimensions (WxHxD) (mm) 1,000 x 650 x 200 
    • Shipping Dimensions (WxHxD) (mm) 1,080 x 730 x 300 

Technical Support

Manual Download

DVM, Ceiling, Heat Pump R410a, Indoor Unit (AM056FNCDEH/EU)

Manuals

2016.04.28

User Manual ver 08

(ENGLISH)

2016.04.28

Safety Guide ver 1.0

(ENGLISH, FRENCH, GERMAN, GREEK, HUNGARIAN, ITALIAN, NEPALI, POLISH, PORTUGUESE, RUSSIAN, SPANISH)

2016.04.28

User Manual ver 08

(FRENCH)

2016.04.28

User Manual ver 08

(PORTUGUESE)