AM040NXMDGR/EU

DVM S Mini HR, Heat Recovery, 3 PHASE, 12.1kW

Heat and cool separate zones simultaneously Compact Chassis & 4 Ways Directional Piping Flexible piping lengths, allowing greater design flexibility

Simultaneous Cooling & Heating

Zoning solutions

Heat Recovery systems add the capability to heat and cool separate zones simultaneously, making it a reliable choice for residential and light commercial applications. A HR Changer is required, and additional MCU’s may be necessary depending on configuration of indoor units, number of indoor units, and connected capacity.

Simultaneous Cooling & Heating

Compact Size for ease of Installation

Compact Chassis & 4 Ways Directional Piping

Compact size and capacity for smaller spaces when using DVM S Mini HR. It offers convenient installation and service flexibility, due to its compact size and 4 ways of piping into the outdoor unit. It can be pipe from the front, side, bottom, or from the rear of the unit.

Compact Size, Easy Installation

Energy Efficiency

Advanced Compressor Technology

DVM S Mini HR delivers energy efficiency* for today's energy conservation, using advanced compressor technology.

High Energy Efficiency

*In comparison to Samsung Heat pump models AM040FXMDEH/EU, AM050FXMDEH/EU, AM060FXMDEH/EU.

Install the Outdoor Unit Almost Anywhere

Broad installation options

DVM S Mini HR provides good allowable piping lengths, allowing greater design flexibility. Its extended piping length of up to 150m and installation height of up to 50m allows installation of indoor unit far from outdoor unit.**

**Max height and length may vary by combination of IDU and ODU.

Install the Outdoor Unit Almost Anywhere

**Max height and length may vary by combination of IDU and ODU.

Specification
  • Technical Information
    • Type DVM S Mini HR
  • Model Name
    • Outdoor Unit AM040NXMDGR/EU
  • Power Supply (Outdoor Unit) [Φ, #, V, Hz]
    • 3Ф, 380~415V, 50Hz
  • Airflow
    • Mode HR
  • Performance (nominal)
    • 4 HP
  • Capacity
    • Cooling (Min / Std / Max) 12.1 kW
    • Heating (Min / Std / Max) 12.1 kW
  • Power Input (Nominal)
    • Cooling 1) 2.69 kW
    • Heating 2) 2.52 kW
  • Current Input (Nominal)
    • Cooling 1) 4.1 A
    • Heating 2) 3.8 A
  • Circuit Amps
    • MCA 16.1 A
    • MFA [A] 20.0 A
  • Energy Efficiency
    • EER (Std, Cooling) 4.5
    • COP (Std, Heating) 4.8
  • Compressor
    • Type Twin BLDC Rotary
    • Output(kW) 4.04 kW
    • Model UG5TK5450FJX x 1
    • Oil (Type) PVE
    • Oil (Initial Charge) [cc] 1700 cc
  • Indoor Unit Fan
    • Type Propeller
    • Motor (Output) [W] 125 W
    • Number of Unit (EA) 2 EA
    • Air Flow Rate [m3/h] 6000 ㎥/h
  • Piping
    • Liquid Pipe (Φ, mm) 9.52 mm
    • Liquid Pipe (Φ, inch) 3/8"
    • Gas Pipe (Φ, mm) 15.88 mm
    • Gas Pipe (Φ, inch) 5/8"
    • Installation Max. Length [m] 150 m
    • Installation Max. Height [m] 50 m
  • Refrigerant
    • Type R410A(Contains fluorinated greenhouse gas, GWP=2,088)
    • Factory Charging (kg) 3.20 kg
    • Factory Charging (tCO2e) 6.68 tCO2e
  • Noise Level (Outdoor)
    • Sound Pressure 50 dBA
    • Sound Power 68 dBA
  • External Dimension (Outdoor Unit)
    • Net Weight (Indoor) 95.0 kg
    • Net Weight (Outdoor) 105.0 kg
    • Unit Dimension (Indoor, WxHxD) 940 x 1210 x 330 mm
    • Unit Dimension (Outdoor, WxHxD) 995 x 1388 x 426 mm
  • Operating Temp. Range
    • Cooling (℃) -5.0 ~ 48.0 ℃
    • Heating (℃) -25.0 ~ 26.0 ℃

Technical Support