Specs

Ceiling Concealed CAC AC072JNHPCC/MG (AC072JNHPCC/MG)

Features
  • Type HSP Duct
Model Name
  • Indoor Unit AC072JNHPCC/MG
  • Outdoor Unit AC072JXQRHC/MG
System
  • Mode Cooling Only
Capacity
  • Cooling [kW] 6.0/17.5/20.0 kW
  • Cooling [Btu/h] 20,500/60,000/68,200 Btu/h
  • Heating [kW] -
  • Heating [Btu/h] -
Power Input (Nominal)
  • Cooling 1) 1.3/5.17/7.3 kW
  • Heating 2) -
Current Input (Nominal)
  • Cooling 1) 2.3/8.1/16.1 A
  • Heating 2) -
Power
  • MCA [A] -
  • MFA [A] -
Energy Efficiency
  • EER (Nominal Cooling) 3.4
  • COP (Nominal Heating) -
  • Energy Grade (Cooling) SAUDI MEPS
  • Energy Grade (Heating) -
Piping Connections
  • Liquid Pipe (Φ, mm) 9.52 mm
  • Liquid Pipe (Φ, inch) 3/8"
  • Gas Pipe (Φ, mm) 19.05 mm
  • Gas Pipe (Φ, inch) 3/4"
  • Installation Max. Length [m] 75 m
  • Installation Max. Height [m] 30 m
Field Wiring
  • Power Source Wire -
  • Transmission Cable -
Refrigerant
  • Type R410A
  • Control Method EEV
  • Factory Charging (kg) 2.6 kg
Power Supply (Indoor Unit) [Φ, #, V, Hz]
1,2,230,60
Fan
  • Type Sirocco Fan
  • Motor (Output) [W] -
  • Number of Unit (EA) 2 EA
  • Air Flow Rate (High / Mid / Low) [CMM] 71/60/50 CMM
  • Air Flow Rate(High/Mid/Low)[L/S] 1,183/1,000/833
  • External Static Pressure (Min / Std / Max) [mmAq] -
  • External Static Pressure (Min / Std / Max) [Pa] 50/60/120 Pa
Drain
  • Drain Pipe (Φ,mm) VP25 (OD 32,ID 25)
Sound
  • Sound Pressure (High / Mid / Low) [dB(A)] 43.0 / 39.0 / 35.0 dBA
  • Sound Power (Cooling) [dB(A)] -
External Dimension (Indoor Unit)
  • Net Weight(kg) 82.5 kg
  • Shipping Weight (kg) 92 kg
  • Net Dimensions (WxHxD) (mm) 1350 x 450 x 910 mm
  • Shipping Dimensions (WxHxD) (mm) 1612 x 519 x 984 mm
Panel Size
  • Panel model -
  • Panel Net Weight (kg) -
  • Shipping Weight (kg) -
  • Net Dimensions (WxHxD) (mm) -
  • Shipping Dimensions (WxHxD) (mm) -
Additional Accessories
  • Drain Pump MDP-G075SP(/Q)
  • Drain Pump Max. Lifting Height/Displacement -
  • Air Filter -
Power Supply (Outdoor Unit) [Φ, #, V, Hz]
3,4,400,60
Compressor
  • Type Twin BLDC Rotary
  • Model UG5T450FXAJX
  • Output(kW) 13.624 kW
  • Oil (Type) PVE
  • Oil (Initial Charge) [cc] 1700 cc
Fan (Outdoor Unit)
  • Air Flow Rate (Cooling) [CMM] 110 CMM
  • Air Flow Rate (Cooling) [L/S] 1833
Sound (Outdoor Unit)
  • Sound Pressure (Cooling / Heating) [dB(A)] 55.0 dBA
  • Sound Power (Cooling) [dB(A)] -
External Dimension (Outdoor Unit)
  • Net Weight(kg) 90 kg
  • Shipping Weight (kg) 100 kg
  • Net Dimensions (WxHxD) (mm) 940 x 1420 x 330 mm
  • Shipping Dimensions (WxHxD) (mm) 995 x 1598 x 426 mm
Operating Temp. Range
  • Cooling (℃) -15 ~ 52℃
  • Heating (℃) -

Need help? Contact Us for Support.

Online

Monday-Sunday (Including Public Holidays)
8:00 AM - 8:00 PM

Email

We'll respond within 24 hours of your request.

Email to CEO

Contact the dedicated CEO's Office.

Call Support 24/7

Digital Appliances Hotline:

(02) 422-2111 [Standard Landline]
1-800-10-7267864 [PLDT Subscribers]
1-800-8-7267864 [Globe Subscribers]

Mobile Phones & Tablets Hotline:

(02) 422-2177 [Standard Landline]
1-800-10-7267777 [PLDT Subscribers]
1-800-8-7267777 [Globe Subscribers]

* For Toll Free numbers, just directly dial 1-800 followed by the network number.

Face to Face Support

Samsung Service Centers

Find out more about how you can get face to face help.

* For any printer related enquiries please visit HP website .